Types
iLOGPlus-GSM
The device carries a built-in
GSM / GPRS modem and can automatically connect via a mobile telephony
network to an ISP provider, to transmit its data via email or ftp
and alarms via email or SMS. The unit controls the internal modem
power supply for power saving purposes in applications with battery
operation.
iLOGPlus-LAN
The device carries
a built-in Ethernet/LAN adaptor and can be directly hooked on to
a local network. It can connects via gateway or a GSM network router
to the Internet. SMS alarming is supportedwith an external GSM modem
attached on the local serial port.
iLOGPlus-EDM
The device supports
any PSTN or wireless modem, including satellite modems, using the
standard Hayes command set. SMS alarming is supported with an external
GSM/GPRS modem. It uses a dial up connection to connect to the ISP
provider and send data and alarms. The unit provides an internal
contact to control the modem supply for power saving purposes and
safe operation (Modem reset).
An iLOG-LAN
unit is permanently installed and is accessible from the whole world!
You can view its web page or interact with the unit: set parameters,
get measurements via email, etc.
|
iLOGPlus™
RTU/Dataloggers
iLOGPlus RTU/Data loggers
are internet enabled devices specially suited for remote data acquisition,
distributed telemetry and remote control. The units act as master
devices and send alarms and data files on their own via FTP, email
and SMS.
All unit types carry a built-in TCP/IP webserver with live webpages
that can be accessed by any Internet browser application. They accept
and serve TCP and SMS commands for interactive operation in a SCADA
system.
Analog inputs and digital I/O are expandable by means of I/O expansion
modules, plugging on a serial I/O expansion bus.

Technical characteristics
The following characteristics
are common to all 3 device types distinguished by the physical communication
medium :
- 4 high resolution analog inputs (AI1-AI4). Range selection between
0-1 Volt, 0-20 mA, 0-20/4-20 mA, PT100, RTD and AD592 temperature
sensors. Two alarm limit definition capability for each analog channel.
Analog inputs can be expanded to 16 by means of 3 GE-AI-4 modular
expansion modules.
- 4 digital inputs for state recording and alarming. Two of them
have pulse counting capability up to 3 KHz supporting sensors with
pulse output (power meters, flow meters, etc.). Digital inputs can
be expanded to 16 by means of 3 GE-DIO-42 modular expansion modules.
- 2 digital relay outputs that are user (for remote control) or
alarm triggered. Digital outputs can be expanded to 8 by means of
3 GE-DIO-42 modular expansion modules.
- External DIN rail adaptor with screw terminals for convenient
wiring.
- Power fail safe memory for up to 40,000 channel records.
- Alarm recording and annunciation via email and SMS.
-
Scheduled data transmission via email file attachement and FTP.
- TCP and SMS ASCII commands for parameter setting and remote control.
- Internal web server publishing a two pages HTML site on the internet,
allowing real time monitoring of the measurements and operating
states and allowing limited parameter changing.
- Serial communication RS232 port supporting local communication
and convenient parameter setting and firmware upgrading using a
PC and the powerful iLOGPlus Transporter utility.
|
|