<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>M2M Αρχεία - Infinite Informatics</title>
	<atom:link href="https://www.infinite.com.gr/case-study-category/m2m/feed/" rel="self" type="application/rss+xml" />
	<link>https://www.infinite.com.gr/case-study-category/m2m/</link>
	<description>IoT Solutions, Cloud Software &#38; Autonomous RTUs</description>
	<lastBuildDate>Thu, 26 Nov 2020 15:20:45 +0000</lastBuildDate>
	<language>en-US</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	

<image>
	<url>https://www.infinite.com.gr/wp-content/uploads/2020/11/infinite_SL_0.png</url>
	<title>M2M Αρχεία - Infinite Informatics</title>
	<link>https://www.infinite.com.gr/case-study-category/m2m/</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>ARC-10: A building block for M2M</title>
		<link>https://www.infinite.com.gr/case_study/arc-10-a-building-block-for-m2m/</link>
		
		<dc:creator><![CDATA[it@mms-adv.gr]]></dc:creator>
		<pubDate>Fri, 16 Oct 2020 06:51:34 +0000</pubDate>
				<guid isPermaLink="false">https://www.infinite.com.gr/?post_type=case_study&#038;p=5654</guid>

					<description><![CDATA[<p>Το άρθρο <a href="https://www.infinite.com.gr/case_study/arc-10-a-building-block-for-m2m/">ARC-10: A building block for M2M</a> εμφανίστηκε πρώτα στο <a href="https://www.infinite.com.gr">Infinite Informatics</a>.</p>
]]></description>
										<content:encoded><![CDATA[<div class="wpb-content-wrapper"><div id="tm-row-6a0375c6ab638" class="vc_row vc_row-outer vc_row-fluid"><div id="tm-column-6a0375c6ac104" class="wpb_column vc_column_container vc_col-sm-1"><div class="vc_column-inner "><div class="wpb_wrapper"></div></div></div><div id="tm-column-6a0375c6ac2b5" class="wpb_column vc_column_container vc_col-sm-10"><div class="vc_column-inner "><div class="wpb_wrapper">
	<div class="wpb_text_column wpb_content_element" >
		<div class="wpb_wrapper">
			<div class="tabs">
<div class="tabs">
<div class="tabs">
<div class="tabs"><span style="color: #222222; font-size: 22px; font-weight: bold;">Introduction</span></div>
<div class="region region-content">
<div id="block-system-main" class="block block-system">
<div class="content">
<div id="node-254" class="node node-case-study node-full clearfix">
<div class="content clearfix">
<div class="field field-name-body field-type-text-with-summary field-label-hidden">
<div class="field-items">
<div class="field-item even">
<p>Infinite ARC-10 is a GSM controller for alarming and remote control via SMS. It is designed to meet the requirements of a wide range of applications from simple to complex. An ARC-10 is capable to communicate with other ARC-10 devices to perform M2M control functions.<br />
Using machine to machine (M2M) SMS commands ARC-10 devices, on event can send commands to other ARC-10 devices to perform a local action. For example at a water tank a low level digital event can trigger an SMS message to a remote pump station to start a pump to refill the tank.<br />
Any number of ARC-10 units can communicate with each other using the M2M functionality. Digital transition events can trigger M2M messages to remote stations and maintenance personnel.<br />
The ARC-10 can interact concurrently with users and any number of other M2M devices like the SCOM-100, BSC-50, or ADU-500.</p>
<h2>Example</h2>
<p>We give below an example of a simple application between two ARC-10 units, where a digital input on the first ARC-10 unit causes a relay output to close for 2 seconds on the remote ARC-10 unit.</p>
</div>
</div>
</div>
<div class="field field-name-field-img-case field-type-image field-label-hidden">
<div class="field-items">
<div class="field-item even"><img decoding="async" src="https://www.infinite.com.gr/wp-content/uploads/2020/10/M2M_ARC_0.jpg" /></div>
</div>
</div>
<div class="field field-name-field-moretext field-type-text-with-summary field-label-hidden">
<div class="field-items">
<div class="field-item even">
<p>You will need 2 SIM cards without PIN number, plus an administrator phone number. Programming can be done with the the ARC-10 Configurator, with the Windows Hyperterminal or with SMS messages to the devices.<br />
<strong>ARC-10, Unit 1 Setup</strong></p>
<table style="width: 100%;">
<tbody>
<tr>
<td style="width: 51.0949%;">To set an administrator</td>
<td style="width: 48.9051%;">1234UN:Administrator phone number&#8221; <sup>1)</sup></td>
</tr>
<tr>
<td style="width: 51.0949%;">To set Unit 2 as a user</td>
<td style="width: 48.9051%;">1234UN:Unit 2 phone number</td>
</tr>
<tr>
<td style="width: 51.0949%;">To disable SMS responses</td>
<td style="width: 48.9051%;">1234RSPD</td>
</tr>
<tr>
<td style="width: 51.0949%;">To enable M2M functionality</td>
<td style="width: 48.9051%;">1234M2M:1 <sup>2)</sup></td>
</tr>
<tr>
<td style="width: 51.0949%;">To set the type of alarming on DI1 to 0 to 1 transition</td>
<td style="width: 48.9051%;">1234I1AM:0</td>
</tr>
<tr>
<td style="width: 51.0949%;">To set the M2M message for Unit 2</td>
<td style="width: 48.9051%;">1234E1:1234O2ON</td>
</tr>
</tbody>
</table>
<p><strong>ARC-10, Unit 2 Setup</strong></p>
<table>
<tbody>
<tr>
<td>To set an administrator</td>
<td>1234UN:Administrator phone number</td>
</tr>
<tr>
<td>To set Unit 1 as a user</td>
<td>1234UN:Unit 1 phone number</td>
</tr>
<tr>
<td>To disable SMS responses</td>
<td>1234RSPD</td>
</tr>
<tr>
<td>To set the ON duration for output 2 to 2 seconds</td>
<td>1234O2:2</td>
</tr>
</tbody>
</table>
<p><sup>1)</sup> &#8220;1234&#8221;: Unit password<br />
<sup>2)</sup> M2M functionality disables the Station name being transmitted as a header in alarm messages</p>
<p>Read more at,</p>
<p><img decoding="async" class="file-icon" title="application/pdf" src="https://www.infinite.com.gr/modules/file/icons/application-pdf.png" alt="" /><a href="/docs/Case_Studies/ARC-10, A building block for M2M v2.pdf" target="_blank" rel="noopener noreferrer"> ARC-10, A building block for M2M.pdf</a></p>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>

		</div>
	</div>
</div></div></div><div id="tm-column-6a0375c6ac754" class="wpb_column vc_column_container vc_col-sm-1"><div class="vc_column-inner "><div class="wpb_wrapper"></div></div></div></div>
</div><p>Το άρθρο <a href="https://www.infinite.com.gr/case_study/arc-10-a-building-block-for-m2m/">ARC-10: A building block for M2M</a> εμφανίστηκε πρώτα στο <a href="https://www.infinite.com.gr">Infinite Informatics</a>.</p>
]]></content:encoded>
					
		
		
			</item>
		<item>
		<title>M2M Reservoir Level Control</title>
		<link>https://www.infinite.com.gr/case_study/m2m-reservoir-level-control/</link>
		
		<dc:creator><![CDATA[it@mms-adv.gr]]></dc:creator>
		<pubDate>Wed, 07 Oct 2020 08:24:13 +0000</pubDate>
				<guid isPermaLink="false">https://www.infinite.com.gr/?post_type=case_study&#038;p=5129</guid>

					<description><![CDATA[<p>Το άρθρο <a href="https://www.infinite.com.gr/case_study/m2m-reservoir-level-control/">M2M Reservoir Level Control</a> εμφανίστηκε πρώτα στο <a href="https://www.infinite.com.gr">Infinite Informatics</a>.</p>
]]></description>
										<content:encoded><![CDATA[<div class="wpb-content-wrapper"><div id="tm-row-6a0375c6ad2e0" class="vc_row vc_row-outer vc_row-fluid"><div id="tm-column-6a0375c6ad3db" class="wpb_column vc_column_container vc_col-sm-1"><div class="vc_column-inner "><div class="wpb_wrapper"></div></div></div><div id="tm-column-6a0375c6ad48c" class="wpb_column vc_column_container vc_col-sm-10"><div class="vc_column-inner "><div class="wpb_wrapper">
	<div class="wpb_text_column wpb_content_element" >
		<div class="wpb_wrapper">
			<div class="tabs">
<div class="tabs">
<div class="tabs">
<div class="tabs">
<div class="tabs">
<div class="tabs"><span style="color: #222222; font-size: 22px; font-weight: bold;">Introduction</span></div>
<div class="region region-content">
<div id="block-system-main" class="block block-system">
<div class="content">
<div id="node-232" class="node node-case-study node-full clearfix">
<div class="content clearfix">
<div class="field field-name-body field-type-text-with-summary field-label-hidden">
<div class="field-items">
<div class="field-item even">
<p>The water level regulation of a reservoir, used for irrigation purposes, is the requirement for an M2M control system. The reservoir is located in an off-grid area, on a hill. A pump house located below the hill, feeds the reservoir from a near river. The system is shown in the figure below.</p>
</div>
</div>
</div>
<div class="field field-name-field-img-case field-type-image field-label-hidden">
<div class="field-items">
<div class="field-item even"><img decoding="async" src="https://www.infinite.com.gr/wp-content/uploads/2020/10/M2M_Level72.jpg" /></div>
</div>
</div>
<div class="field field-name-field-moretext field-type-text-with-summary field-label-hidden">
<div class="field-items">
<div></div>
<div></div>
<div class="field-item even">
<h2>Proposal</h2>
<p>A BSC-50E battery powered RTU with an ultrasonic sensor, is used for tracking the reservoir water level. BSC-50E sends M2M commands to an ARC-10 GSM controller, which controls the pump operation through its relay outputs. The pump automation system (e.g. a PLC) supports the following functions:</p>
<table>
<tbody>
<tr>
<th>Function</th>
<th>Actuator / Indicator</th>
<th>Action</th>
</tr>
<tr>
<td>Start Operation</td>
<td>Push button (Start button)</td>
<td>Enable Remote control,<br />
Turn Pump ON for t=T1 <sup>1)</sup></td>
</tr>
<tr>
<td>Stop Operation</td>
<td>Push button (Stop button) or<br />
Digital input IN1</td>
<td>High pulse on IN1&#8211;&gt; Cancel system operation</td>
</tr>
<tr>
<td>Remote Control</td>
<td>Digital input IN2</td>
<td>High to Low transition &#8211;&gt; Turn Pump ON for t=T2 <sup>2)</sup>,<br />
Low to High transition &#8211;&gt; Stop PUMP)</td>
</tr>
<tr>
<td>Thermal protection</td>
<td>Digital output OUT1</td>
<td>Low &#8211;&gt; Normal operation,<br />
High &#8211;&gt; Protection active (Operation cancelled)</td>
</tr>
</tbody>
</table>
<p><sup>1)</sup> T1 is the time, depending on the pump flow rate, needed to fill the reservoir from empty state to a level between H and HH.<br />
<sup>2)</sup> T2 is the time it takes to reach a level between H and HH, starting with water level L.</p>
<p>ARC-10 outputs DO1, DO2 are connected to IN1 and IN2 of the pump control system respectively. The thermal protection indication (OUT1) is connected to ARC-10, digital input 1 (DI1).<br />
On the other side, an ultrasonic sensor (Massa M300) is connected to BSC-50E, analog input 1 (AI1). Two alarm limits are set on the analog measurement:</p>
<ul class="nop">
<li>Alarm limit low, which corresponds to level L.</li>
<li>Alarm limit high, which corresponds to level H.</li>
</ul>
<p>The water level is logged every hour. A level switch, indicating the HH water level, is connected to BSC-50E, digital input 1 (DI1).</p>
<h2>Operation description</h2>
<p>After start up, the pump feeds the reservoir, until the water level reaches the high limit (Level H). In the meantime BSC-50E scans the water level every minute.<br />
On reaching the high limit, BSC-50E sends an M2M SMS, commanding the ARC-10 unit to switch DO2 on. The pump is turned off. At the same time, BSC-50E switches level scanning to a lower rate (e.g. every 15 minutes), to save power.<br />
The pump remains in the hold state until the water level drops, due to irrigation flow, below the low limit. Then BSC-50E sends an SMS, commanding the ARC-10 unit to switch DO2 off. The pump is turned on. At the same time, it switches to higher sampling rate (every minute) to keep track of the reservoir filling.<br />
Once a day, BSC-50E sends the water level logs to a system administrator.</p>
<h2>Alerting</h2>
<p>If the water level reaches, for any reason, the HH limit, the level switch activates an alarm on BSC-50E, DI1. BSC-50E sends an SMS command to the ARC-10 unit, to switch DO1 on for 2 seconds. The feeding system operation is cancelled. An additional SMS is sent to maintenance personnel, alerting for the malfunction.<br />
In case of pump overheating, ARC-10 sends a respective alert to maintenance personnel.</p>
<h2>Battery lifetime</h2>
<p>The lifetime of the BSC-50E internal battery (LSH-20) depends on the water feeding cycles per day, as shown in the table below:</p>
<table>
<tbody>
<tr>
<th>Feeding cycles</th>
<th>M2M SMS</th>
<th>Daily consumption [mAh]</th>
<th>Battery Lifetime [Years]</th>
</tr>
<tr>
<td>2</td>
<td>4</td>
<td>16.7</td>
<td>2.13</td>
</tr>
<tr>
<td>4</td>
<td>8</td>
<td>20.2</td>
<td>1.76</td>
</tr>
<tr>
<td>6</td>
<td>12</td>
<td>24.6</td>
<td>1.44</td>
</tr>
<tr>
<td>8</td>
<td>16</td>
<td>31.0</td>
<td>1.14</td>
</tr>
<tr>
<td>10</td>
<td>20</td>
<td>37.4</td>
<td>0.95</td>
</tr>
</tbody>
</table>
<p>Read more at,</p>
</div>
</div>
</div>
<div class="field field-name-field-doc-case field-type-file field-label-hidden">
<div class="field-items">
<div class="field-item even"><span class="file"><img decoding="async" class="file-icon" title="application/pdf" src="https://www.infinite.com.gr/modules/file/icons/application-pdf.png" alt="" /> <a href="/docs/Case_Studies/M2M Reservoir Level Control.pdf" target="_blank" rel="noopener noreferrer" type="application/pdf; length=346636">M2M Reservoir Level Control.pdf</a></span></div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
<div class="region region-content">
<div id="block-system-main" class="block block-system">
<div class="content">
<div id="node-102" class="node node-case-study node-full clearfix">
<div class="content clearfix">
<div class="field field-name-field-doc-case field-type-file field-label-hidden">
<div class="field-items"></div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>
</div>

		</div>
	</div>
</div></div></div><div id="tm-column-6a0375c6ad652" class="wpb_column vc_column_container vc_col-sm-1"><div class="vc_column-inner "><div class="wpb_wrapper"></div></div></div></div>
</div><p>Το άρθρο <a href="https://www.infinite.com.gr/case_study/m2m-reservoir-level-control/">M2M Reservoir Level Control</a> εμφανίστηκε πρώτα στο <a href="https://www.infinite.com.gr">Infinite Informatics</a>.</p>